How often do the Electrical Regulations say that a Electrical Installation Condition Report is required?

How often is an Electrical Installation Condition Report (EICR) required?

 

Electrical Regulations
Electrical installations should be Inspected and Tested as follows:

The table below provides guidance on the frequency of formal inspections of electrical installations as well as routine checks. (Table extracted from BS7671 IET Wiring Regulations 18th Edition: 2018).

Type of Installation

Routine check

Maximum period between
inspections and testing
as necessary

General Installation

   

Domestic accommodation -
general
Domestic accomomdation -
rented houses and flats

-

1 year

change of occupancy/10 years
change of occupancy/5 years

Residential accommodation (Houses of
Multiple Occupation) - halls of residence,
nurses accommodation, etc.

1 year

change of occupancy/5 years

Educational establishments

6 months

5 years

Industrial

1 year

3 years

Commercial

1 year

Change of occupancy/5 years

Offices

1 year

5 years

Shops

1 year

5 years

Laboratories

1 year

5 years

Hospitals and Clinics

   

Hospitals and medical clinics -
general areas
Hospitals and medical clinics -
medical locations

1 year

6 months

5 years

1 year

Buildings open to the public

   

Cinemas

1 year

1-3 years

Church installations

1 year

5 years

Leisure complexes
(excluding swimming pools)

1 year

3 years

Places of public entertainment

1 year

3 years

Restaurants and hotels

1 year

5 years

Theatres

1 year

3 years

Public houses

1 year

5 years

Village halls/Community centres

1 year

5 years

Special and specific installations
(for medical locations see above)

   

Agricultural and horticultural

1 year

3 years

Swimming pools

4 months

1 year

Caravans
Caravan parks

1 year
6 months

3 years
1 year

Highway power supplies

as convenient

6-8 years

Marinas

4 months

1 year

Fish farms

4 months

1 year

Emergency lighting

daily/monthly

3 years

Fire alarms

daily/weekly

1 year

Launderettes

monthly

1 year

Petrol filling stations

1 year

1 year

Construction site installations

3 months

3 months

 

 

For further Information, please do not hesitate to contact us.

Telephone: 01892 531728

Email: karen@brightsparkelectrician.co.uk

 

Related Articles

Your electrician Philip was punctual, friendly and very efficient. Would certainly use you again and recommend your company.

Ian - Tunbridge Wells

I’d like to say a huge thank you Karen, to you & your team for providing the excellent service you do. Always there when we have an issue or just routine work needs to be carried out. It’s so reassuring that we can rely on you at any time, even for advice. Always professional, knowledgeable & particularly personable Superb…

Kerry, Tunbridge Wells

Thank you very much, and please pass on my thanks to Philip who completed the job. I appreciate it was an awkward space for him to work on, but everything was done so well and so quickly - I am very happy with the outcome! Will be returning to you for more jobs soon I’m sure!

Rebecca - Tonbridge

Prompt courteous service, with very competitive rates. I have no reservations to recommend this Company.

Christophe, Wadhurst

"I have had Bright Sparks at my property twice in the last six months to complete some electrical work. I have been blown away by the innovative efficient way I am communicated with the efficiency and ease of the process. The work has been carried out to a more than satisfactory standard and I found it to be extremely competitively priced. It is by far the best experience I have had with any service provider in forever. Thanks guys."